UNILOG 300

UNILOG 300 -discontinued-

The UNILOG 300 was produced from January 2013 to April 2021. On this page, you will find the relevant product information for this product. The UNILOG 300 is no longer available and has been succeeded by the UNICOM 300. You can find more information about the UNICOM 300 here.

UNILOG 300 is a GSM /GPRS modem for UNIGAS with in addition an optional standalone data log function. Signal inputs are equipped with an EX-barrier. This allows UNILOG 300 to be connected directly with devices like UNIGAS or a gas meter in a hazardous area. An internal antenna is standard equipment, connection to with an (optional) external antenna is possible. UNILOG 300 is available in an battery powered version and a 230 VAC version.

Depending on its functionality the microprocessor processes functions like pulse counting, reading of an encoder, storage of data, communications via GSM/GPRS, scheduler (for battery powered version), activation of GSM/GPRS connection and preparing and transmitting logged data via FTP.

UNILOG 300

Battery-powered version

  • Battery life time more than 10 year (depending from the read out frequency and battery package)
  • Available as 2-Channel data logger
  • Remote reading via GSM data, GPRS TCP (pull) or FTP (push)
  • Easy to install and ready for wall mounting
  • ATEX approved, installation outside the Ex-area
  • Suited for meter reading of encoder: Itron, GWF, Elster, Dresser, FMG, GFO, Aerzen
  • Standard with internal antenna, external antenna optional
  • Two serial ports for 2 UNIGAS 300 devices
  • Intrinsically safe circuits which enables connection to devices in the Ex-area
  • Timer/ scheduler for GSM/GPRS module, day and month
  • Communication IEC 1107 (62056-21), mode C VDEW 2.0 protocol
  • POSIX Clock
  • Protection class IP65, may be placed outdoors

Mains-powered version

  • Power supply 230 VAC or 12 VAC or 12 – 15 VDC
  • Communication IEC 1107 (62056-21), mode C VDEW 2.0 protocol
    2-Channel data logger
  • Suited for meter reading of encoder: Itron, GWF, Elster, Dresser, FMG, GFO, Aerzen
  • One serial port for connection to UNIGAS 300
  • Power supply for UNIGAS 300
  • 3 connectors for modules; pulse out (2 x 2) pulses, RS485, RS232
  • Standard supplied with a local bus for maximum 3 x ISC 230B, maximum distance 50m
  • Ex earthing is not necessary due to intrinsic safe circuits
  • Ex approved, for installations in the safe area
  • Connections to the Ex-area are allowed, due to the intrinsically safe circuits
  • Standard with internal antenna, external antenna optional
  • POSIX Clock
  • Protection class IP65, may be placed outdoors

Wij maken gebruik van cookies op onze website. Wir verwenden Cookies auf unserer Website. We make use of cookies on our website. lees meer

De cookie-instellingen op deze website zijn ingesteld op "toestaan" om u de beste gebruikerservaring te bieden. Bij het verder gebruikmaken van deze website, zonder uw cookie-instellingen te wijzigen of door op "Accepteren"te klikken, gaat u hiermee akkoord.

The cookie settings on this website are set to "allow" to give you the best user experience. By further use of this website, without changing your cookie settings or by clicking on "Accept", you agree.

Die Cookie-Einstellungen auf dieser Website sind auf "Zulassen" eingestellt, um Ihnen die bestmögliche Nutzererfahrung zu bieten. Wenn Sie diese Website weiter nutzen, ohne Ihre Cookie-Einstellungen zu ändern oder auf "Akzeptieren" zu klicken, stimmen Sie zu.

Ok